Diesel Generator EDM L180LR (S)
|
Constant power |
1 50 kW |
|
Reserve power |
188 kW |
|
Voltage |
230 / 400 V |
|
Frequency |
50 Hz |
|
Number of phases |
three-phase |
|
Primary diesel engine |
Lister Petter LP665G3 |
|
Synchronous generator |
Leroy Somer TAL-A44-M |
|
Controller |
DSE6120 |
|
Execution |
in a noise-proof casing |
|
Dimensions (L x W x H) |
3502x1150x1882 mm |
|
Weight |
2363 kg |
|
Fuel consumption at 100% load |
39.7 l/hour |
|
Fuel consumption at 75% load |
29.5 l/hour |
|
Fuel tank |
495 l |
|
Autonomy |
min. 8 ocloc'k |
|
Engine |
|
|
Constant power |
168 kW |
|
Reserve power |
185 kW |
|
Rotation frequency |
1500 rpm |
|
Engine capacity |
6.5 l |
|
Number and arrangement of cylinders |
6 cylinders, in-line, vertical |
|
Bore x Stroke (mm x mm) |
105 x 124 |
|
Speed control accuracy |
+/- 5% |
|
Generator |
|
|
Constant power |
160 kW |
|
Reserve power |
200 kW |
|
Voltage |
230 / 400 V |
|
Frequency |
50 Hz |
|
Type of current |
alternating, three-phase |
|
Number of poles |
4 |
|
Power factor COS Ф |
0.8 |
|
Type |
synchronous, brushless, single bearing |
|
Excitation system |
self-stimulation |
|
Voltage adjustment |
automatic |
|
Protection class |
IP 23 |
|
Insulation class |
H |
|
Lubrication system |
|
|
Lubrication system |
combined pressure and spray |
|
Oil pump type |
gear type, camshaft driven |
|
Oil filter type |
full flow cartridge filter |
|
Oil type |
SAE 15W40 / 10W30 |
|
Cooling system |
|
|
Cooling type |
liquid (radiator), circulation under pressure |
|
Coolant type |
GOST 28084-89 |
|
Maximum coolant temperature |
103 ºС |
|
Water pump |
centrifugal type with belt drive |
|
Electrical system |
|
|
System voltage |
24 B |
|
Starting device |
electric starter |
|
Maximum charging generator current |
25 A |
|
Accumulator battery |
24 V / 100 A*h |
|
Air supply system |
|
|
Type |
naturally aspirated |
|
Air filter type |
filter element |
|
Gas exhaust system |
|
|
Exhaust gas temperature |
550 ºС |
|
Exhaust gas flow |
9 m³/h |
|
Muffler type |
industrial - 9 dB |
|
Maximum exhaust back pressure |
9.8 kPa |
|
Noise hood |
|
|
Purpose |
Effective protection from adverse environmental factors, protection from unauthorized access, high level of noise protection |
|
Housing material |
steel 2 mm |
|
Noise level (7m) |
50 dB |
|
Coloring |
powder coating |
|
terms of Use |
outdoor use |
|
Control Panel |
|
|
Control Panel |
based on DSE6120 controller |
|
Main functions |
- control of diesel electric unit |
|
- signaling of warnings and accidents |
|
|
- supply voltage for own needs |
|
|
- display on the LCD display the values of the main operating parameters of the electric generator: frequency, voltage, current, engine speed, oil pressure, coolant temperature, operating hours, number of starts, generated electricity, battery voltage |
|
|
- emergency stop button; - control of main network parameters; - automatic start when the main network parameters deviate from the specified values; - automatic shutdown and transfer of power to the main network when the main network parameters are restored; - recharging batteries; - control of the coolant heater. |
|