UPS ONTEK SPM 40 kVA
(Equipment / Material)
Condition: New
Location or Storage Country: Russia
Service Engineering Support: Yes
Warranty: Yes
Price: Call for price
Overview:
Installed capacity* | 40kVA / 40kW |
Power module capacity | 20kVA / 20kW |
Number of power modules | 2 |
Static bypass | 90 kVA |
Cabinet dimensions, (W×H×D) mm | 600×1475×1100 [30U] |
Batteries | Internal |
Net weight (kg) | 624 |
Phase | 3-phase input / 3-phase output |
Parallel work | up to 2 UPS (with the ability to work with a common battery group) |
Built-in circuit breakers | 3 pcs: main input, output, mechanical bypass |
Starting from battery (cold start) | In stock |
Nominal voltage | 3×380/400/415V (3 phases + neutral) |
Voltage range | 305-478V at 100% load; 208-478V at <70% load |
Nominal frequency | 50/60 Hz (automatic recognition) |
Frequency range | 40-70 Hz |
Power factor | >0.99 at 100% load; >0.98 at 50% load |
Harmonic distortion (THDi) | < 3% at full load |
Nominal voltage | 3×380/400/415V (3 phases + neutral) |
Voltage regulation (steady state) | ≤ ±1% typical (balanced load); ≤ ±2% typical (unbalanced load) |
Nominal frequency | 50/60 Hz |
Frequency range (synchronized range) | 46-54 Hz or 56-64 Hz |
Overload capacity | 1 hour at 110%, 10 minutes at 125%, 1 minute at 150% and 200 ms at >150% |
Harmonic distortion | ≤ 2% THD (linear load); ≤ 4% THD (non-linear load) |
Efficiency | Up to 94.5% |
Number of internal batteries | 40×3×9Ah |
Nominal voltage | +/- 216V (12V x 36 pcs.) |
Maximum voltage | +/- 240V (12V x 40 pcs.) |
Minimum voltage | +/- 192V (12V x 32 pcs.) |
Floating charge | 2.25V/cell |
Accelerated charge | 2.35V/cell |
Battery charging method | Three-stage |
Temperature compensation | In stock |
Maximum charging current (per power module) | 6A |
Operating temperature and humidity | 0-40°C, < 95% non-condensing |
Altitude** | < 1000m for rated power |
IP class | IP 20 |
Smart RS-232×2pcs / USB | Support Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux and MAC |
Dry contacts | Built-in input/output relays: 2 pcs – input signals, 6 pcs – output signals |
EMBS connector | External bypass switch status detection signal contact |
batt. temp connector × 5pcs | For connecting battery charge temperature compensation sensors |
Additional slot | Internal slot for connecting expansion cards × 2 pcs |
SNMP card (optional) | Power management using SNMP manager and web browser |
Modbus card (optional) | Real-time control and monitoring via Modbus RTU protocol |
Optional | Environment sensor (temperature and humidity) Temperature sensor for battery charge thermal compensation - up to 5 pcs. |
Certification | Certificate of conformity EAEU TR CU 004/2011, TR CU 020/2011. Certificate according to ISO 9001:2015 standard. |
Warranty period | 3 years (standard) or extended |
* When the temperature exceeds 30°C, the output power factor decreases to 0.9 at 31-35°C and to 0.8 at 36-40°C.
**If the UPS is installed or used in a location where the altitude is higher than the maximum altitude, the output power will be derated by 1% for every 100m.

OOO "Ontek"
Locations: Moscow region, Mytishchi, Kolpakova street, 42k3
Main Products/Services: Equipment for electrical networks