UPS ONTEK SPM 40 kVA
(Equipment / Material)
Condition: New
Location or Storage Country: Russia
Service Engineering Support: Yes
Warranty: Yes
Price: Call for price
Overview:
| Installed capacity* | 40kVA / 40kW |
| Power module capacity | 20kVA / 20kW |
| Number of power modules | 2 |
| Static bypass | 90 kVA |
| Cabinet dimensions, (W×H×D) mm | 600×1475×1100 [30U] |
| Batteries | Internal |
| Net weight (kg) | 624 |
| Phase | 3-phase input / 3-phase output |
| Parallel work | up to 2 UPS (with the ability to work with a common battery group) |
| Built-in circuit breakers | 3 pcs: main input, output, mechanical bypass |
| Starting from battery (cold start) | In stock |
| Nominal voltage | 3×380/400/415V (3 phases + neutral) |
| Voltage range | 305-478V at 100% load; 208-478V at <70% load |
| Nominal frequency | 50/60 Hz (automatic recognition) |
| Frequency range | 40-70 Hz |
| Power factor | >0.99 at 100% load; >0.98 at 50% load |
| Harmonic distortion (THDi) | < 3% at full load |
| Nominal voltage | 3×380/400/415V (3 phases + neutral) |
| Voltage regulation (steady state) | ≤ ±1% typical (balanced load); ≤ ±2% typical (unbalanced load) |
| Nominal frequency | 50/60 Hz |
| Frequency range (synchronized range) | 46-54 Hz or 56-64 Hz |
| Overload capacity | 1 hour at 110%, 10 minutes at 125%, 1 minute at 150% and 200 ms at >150% |
| Harmonic distortion | ≤ 2% THD (linear load); ≤ 4% THD (non-linear load) |
| Efficiency | Up to 94.5% |
| Number of internal batteries | 40×3×9Ah |
| Nominal voltage | +/- 216V (12V x 36 pcs.) |
| Maximum voltage | +/- 240V (12V x 40 pcs.) |
| Minimum voltage | +/- 192V (12V x 32 pcs.) |
| Floating charge | 2.25V/cell |
| Accelerated charge | 2.35V/cell |
| Battery charging method | Three-stage |
| Temperature compensation | In stock |
| Maximum charging current (per power module) | 6A |
| Operating temperature and humidity | 0-40°C, < 95% non-condensing |
| Altitude** | < 1000m for rated power |
| IP class | IP 20 |
| Smart RS-232×2pcs / USB | Support Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux and MAC |
| Dry contacts | Built-in input/output relays: 2 pcs – input signals, 6 pcs – output signals |
| EMBS connector | External bypass switch status detection signal contact |
| batt. temp connector × 5pcs | For connecting battery charge temperature compensation sensors |
| Additional slot | Internal slot for connecting expansion cards × 2 pcs |
| SNMP card (optional) | Power management using SNMP manager and web browser |
| Modbus card (optional) | Real-time control and monitoring via Modbus RTU protocol |
| Optional | Environment sensor (temperature and humidity) Temperature sensor for battery charge thermal compensation - up to 5 pcs. |
| Certification | Certificate of conformity EAEU TR CU 004/2011, TR CU 020/2011. Certificate according to ISO 9001:2015 standard. |
| Warranty period | 3 years (standard) or extended |
* When the temperature exceeds 30°C, the output power factor decreases to 0.9 at 31-35°C and to 0.8 at 36-40°C.
**If the UPS is installed or used in a location where the altitude is higher than the maximum altitude, the output power will be derated by 1% for every 100m.
OOO "Ontek"
Locations: Moscow region, Mytishchi, Kolpakova street, 42k3
Main Products/Services: Equipment for electrical networks