UPS ONTEK SMRT 1 /wo 1000 VA/W
(Equipment / Material)
Condition: New
Location or Storage Country: Russia
Service Engineering Support: Yes
Warranty: Yes
Price: Call for price
Overview:
Phase | Single phase |
Power | 1000VA/1000W |
Nominal voltage | 220/230/240 V |
Voltage range | 110-300V ±5% at 50% load; 160-300V ±5% at 100% load |
Frequency | 40-70 Hz |
Input connectors | 1 pc IEC C14 |
Power factor | ≥ 0.99 at rated voltage (100% load) |
Harmonic distortion (THDi) | < 5% at nominal input voltage |
Output voltage | 220/230/240 V |
Output connectors | 8 pcs IEC C13 |
Programmable sockets | 4 pcs. |
Voltage stabilization level (battery mode) | ± 1% |
Frequency range (synchronized range) | 47-53 Hz or 57-63 Hz |
Frequency range (battery mode) | 50Hz ±0.1Hz or 60Hz ±0.1Hz |
Crest factor | 3:1 (max) |
Harmonic distortion | ≤ 2% THD (linear load); ≤ 4% THD (non-linear load) |
Overload capacity | 10 min. at 110% load, 1 min. at 125% load, up to 0.5 sec. at 150% load |
Time to switch to battery | Zero |
Time to switch to Bypass | < 4 ms |
Waveform in battery mode | Pure sine wave |
From the network | ≥ 89% when battery is fully charged |
ECO mode | ≥ 96% when battery is fully charged |
Battery operation | ≥ 88% |
Battery type | External |
Battery capacity | up to 150Ah |
Quantity | 2 |
Charging current (max, adjustable) | Default 2A, max 12A |
Charging voltage | 27.4V ±1% |
Battery starting (cold start) | In stock |
LCD display | UPS status, load level, battery charge level, input/output voltage, remaining runtime and error codes. |
Sound notifications | Battery power: Beep every 5 sec. Low battery: Beep every 2 sec. Overload: Beep every 1 sec. Error: Constant beep. |
Dimensions, W×H×D (mm) | 438×88×410 |
Net weight without batteries (kg) | 9.08 |
Operating humidity and temperature | Humidity 0-95% at 0-40°C without condensation |
Noise level | Less than 50 dB at 1 meter |
Smart RS-232 × 1pc, USB × 1pc | Support for Windows, Linux and MAC families |
Optional SNMP | Power management using SNMP manager and web browser |
Optional Modbus | Manage and monitor multiple UPSs in real time via RS-485 communication port |
Certification | Certificate of Conformity EAEU TR CU 004/2011, TR CU 020/2011. Certificate of Conformity in terms of resistance to seismic impacts with an intensity of 9 points on the MSK-64 scale. Certificate according to the ISO 9001:2015 standard |
Warranty period | 3 years (standard) or extended |
Products are constantly being improved. Specifications and appearance are subject to change without notice.