Switchgear for power supply and Control of Electric motors of the RTZO-88 series
1. Purpose and scope of application
Low-voltage switchgear units (LVSU) of the RTZO-88 series are designed for:
- power supply and control of electric drives of shut-off and control valves with a capacity of up to 10 kW and 14–28 kW;
- control of electric motors of auxiliary mechanisms of thermal power plants and nuclear power plants with a capacity of up to 11 kW.
Application area: industry, energy facilities, housing and communal services.
Manufactured according to GOST R 51321, TU 16-536.024-75.
2. Performances (variations)
The devices are available in several modifications, differing in their element base:
| Designation | Peculiarities |
|---|---|
| RTZO-88M | Basic series according to working project OLX.084.215-88M. |
| RTZO-88V | A modernized series, retaining the same schematics and dimensions as the RTZO-88M. Adaptation to automated process control systems has been improved, and external wiring has been simplified. |
| RTZO-88BSE | Schneider Electric components (circuit breakers and starters), diagrams and dimensions are the same as for РТЗО-88В. |
| RTZO-88BSO | Schneider Electric circuit breakers + domestically produced starters, diagrams and dimensions – the same as RTZO-88V. |
| RTZO-88MSE | Schneider Electric components, diagrams and dimensions are the same as for RTZO-88M. |
| RTZO-88SI | Siemens components, circuit diagrams and dimensions are the same as those of the RTZO-88M. |
At customer request, delivery in Rittal designs with imported equipment is possible.
3. Operating conditions
- Ambient temperature: from +5 to +40 °C .
- Altitude above sea level: no more than 2000 m .
- Seismic resistance: up to 9 points according to MSK-64 (upon order).
- Environment: non-explosive, no aggressive gases or vapors.
- Protection class: IP41 (cabinet version).
4. Design and features
- Modular design of switchgear.
- Side walls are installed only on the outer cabinets.
- Wire entry – from above or below.
- Input cabinets are designed to connect up to 8 cables with a cross-section of up to 185 mm² (depending on the design).
- The terminal blocks are located on the cabinet frame, which simplifies the connection of external circuits.
- A unified signaling circuit with indication of circuit breaker tripping on control units.
Dimensions of cabinets (H × W × D):
- 2000(2200) × 800 × 400 mm – single-row without cable assembly;
- 2000(2200) × 1200 × 400 mm – single-row with cable assembly device;
- 2000(2200) × 800 × 800 mm – double-row.
5. Main technical characteristics (excerpt)
5.1. Input cabinets for power supply of valves up to 11 kW (examples)
| Cabinet type | Nom. current, A | Nominal voltage, V | Peculiarities | Dimensions, mm |
|---|---|---|---|---|
| SHOE8331V | 50, 100 | ~380 / ~380 | 1 reactor, 1 switch, without cable assembly | 2000×800×400 |
| SHOE8332V | 50 | ~380 / ~380 | 1 reactor, 2 switches, without cable assembly | 2000×800×400 |
| SHOE8347V | 63, 100 | ~380 / ~380 | With cable assembly device | 2000×1200×400 |
| ШДЭ8331В | 50, 100 | ~380 / ~380 | Double-row, with connection blocks | 2000×800×800 |
5.2. Control units for electric motors of fittings up to 11 kW (example)
| Block type | Purpose | Nom. current, A | Nominal voltage of circuits, V | Dimensions, mm |
|---|---|---|---|---|
| BOE 5401V | Reversible motor control, sealed closing (current relay) | 1.6…25 | ~380 / ~220 | 200×700×150 |
| BOE 5403V | Reversible motor control (with/without additional relay) | 1.6…25 | ~380 / ~220 | 150×700×150 |
| BOE 5101V | Control of the engine of auxiliary mechanisms (local panel) | 1.6…25 | ~380 / ~220 | 300×700×150 |
Modifications with adaptation to the automated process control system (index “VA” at the end of the type) are possible.
5.3. Input cabinets for 14–28 kW valves
| Cabinet type | Service | Nom. current, A | Dimensions, mm |
|---|---|---|---|
| SHOE8335V | one-sided | 63, 100 | 2000×800×400 |
| ШДЭ8335В | two-sided | 63, 100 | 2000×800×800 |
5.4. Intermediate row cabinets for clamps
| Type | Number of clamps | Dimensions, mm |
|---|---|---|
| SHOE 9501V | 520 | 2000×600×400 |
| ШДЭ 9502В | 1560 | 2000×800×800 |
6. Delivery set
Delivery can be carried out in the form of:
- separate cabinets;
- cabinets for assembly into panels at the installation site;
- ready-made panels from several cabinets with inter-cabinet connections.
The set includes:
- cabinets/units according to the order specifications;
- a set of technical documentation (passport, electrical circuit diagram, instructions);
- fasteners for assembling panels (if necessary).
7. Ordering procedure
To place an order, you must fill out a questionnaire indicating:
- type of metal structure;
- block composition of the low-voltage switchgear (according to the RTZO-88M or RTZO-88V design);
- relative position of cabinets and units;
- rated currents of circuit breaker tripping devices.
When ordering several panels, the questionnaire is completed with the main inscription in accordance with GOST 2.104-68.
Developer and manufacturer:
JSC ChEAZ (engineering and production complex "SHCHIT"). Full cycle: design, production, assembly, installation supervision, and maintenance.