Input characteristics of the UPS
Nominal input voltage, V 380 V (optional 400, 415 V) Input voltage range, V 208~478V Input frequency range, Hz 40~70Hz Nominal input current, A Up to 60 amps Input power factor, W ≥ 0.99 Input harmonic distortion coefficient ≤ 5% (at 100% non-linear load) Voltage range in economy mode max +25% (options +10%, +15%, +20%), min -45% (options -20%, -30%) Input connection type Terminal block: three phases, neutral and earth UPS output characteristics
Nominal output voltage, V 220 V (optional 208, 230, 240 V) Output voltage accuracy ± 1% Topology and output voltage waveform Online UPS with "pure" sine wave output Output voltage distortion ≤2% on linear load Output frequency (battery mode), Hz 50, 60 ±0.1 Hz Output power factor, W 0.9 Output connection type Terminal block and 2 sockets IEC320 C13 (10A) UPS Specifications
Peak load factor 3:1 Overload capacity When operating from the mains: up to 110% - 60 minutes, up to 125% - 10 minutes, up to 150% - 1 minute, over 150% - switch to bypass Efficiency in mains mode ≥90% at full load Efficiency in economy mode ≥97% at full load Surge protection, J 300 joules Filtration Built-in filter Bypass type Electronic Bypass voltage range, V From +25% to -45% Bypass frequency range ±10% (adjustable ±1%, ±2%, ±4%, ±5%) Availability of built-in batteries No Battery type Sealed lead acid with leakage protection DC bus voltage, V ±96V, ±108V, ±120VDC (optional) Battery life (50% and 100% load), minutes Depending on the capacity of the connected battery pack Recharge time Depending on the capacity of the connected battery pack Charging mode Intelligent charging with temperature compensated voltage Charging current, A Up to 10 amps Time to switch to batteries 0 ms - from the mains to the battery Battery protection Protection against over-discharge, over-voltage, short circuit Communications and interfaces
Interface ports RS485 or RS232, USB Internal slot for control card Slot for SNMP, Modbus or dry contacts cards Emergency Power Off (EPO) Eat LCD display and indication Digital LCD display and mimic diagram Sound alarm Power failure, low battery, overload, UPS error Working conditions
Operating temperature 0°C ~ 40°C Relative humidity during operation 0 ~ 95% Altitude 0 ~ 3000 meters Storage temperature -25°C ~ +55°C Storage altitude above sea level 0 ~ 10000 meters (recommended) Physical characteristics
Heat dissipation in mains mode 2775 BTU/hour Noise level, dB less than 55 dB Size (W x D x H), mm 443x580x131 (without battery pack) Package size (W x D x H), mm 573x746x230 Net weight, kg 25.0 Gross weight, kg 27.0 Compliance with standards
Protection class IP20 Safety TR CU 004/2011, IEC 62040-1 EMS TR CU 020/2011, IEC 62040-2