Phase | 3-phase input / 3-phase output |
Power | 1200kVA/1200kW |
Parallel work | up to 8 UPS |
UPS type | Modular |
Nominal voltage | 3 x 380/400/415 V (3 phases + neutral) |
Voltage range | 137.9-305.1 V at 40% load; 304.9-485.1 V at 100% load; |
Frequency | 40-70 Hz |
Power factor | ≥ 0.99 at 100% load |
Harmonic distortion (THDi) | ≤ 3% at full linear load |
Output voltage | 380/400/415V (linear); 220/230/240V (phase) |
AC Voltage Regulation (Battery Mode) | ± 1% |
Frequency range (synchronized range) | 45-55 Hz or 54-66 Hz |
Frequency Range (Output) | 50/60 Hz ± 0.1 Hz |
Frequency range (battery mode) | 50/60 Hz ± 0.1% |
Crest factor | 3:1 (max) |
Harmonic distortion | ≤2% THD (linear load); ≤4% THD (non-linear load) |
Time to switch to battery | Zero |
Time to switch to Bypass | Zero |
Waveform in battery mode | Pure sine wave |
Overload capacity | 100–110% for 60 min, 111–125% for 10 min, 126–150% for 1 min; more than 150% 1.2 sec |
Nominal voltage | 3 x 380/400/415 V (3 phases + neutral) |
Voltage range | -30% ÷ +20% (adjustable) |
Frequency range (synchronized range) | 46-54 Hz or 56-64 Hz |
Overload capacity | at 30℃: up to 135% continuous operation; at 40℃: 125% continuous operation; more than 1000% 100ms |
From the network | 96% |
ECO mode | 99% |
Battery type | Lead-acid or lithium batteries |
Nominal DC bus voltage when using lead-acid batteries | adjustable, from 360V to 600V |
Nominal DC bus voltage when using lithium batteries | 512B |
Charging current (max) | 400A |
Module model | MPM60P |
Module power | 60kVA/60kW |
Number of modules | 20 |
Communication interface | RS232 1pc, RS485 2pcs, Parallel 2pcs, LBS 1pc, BMS 1pc, Relay board (optional), SNMP card (optional), NTC temperature sensor port 1pc, Battery temperature sensor port (RS485) 1pc, BACKFEED port 1pc, Battery ground detection signal input port 1pc, USB 1pc, EPO 1pc, 12Vdc external output switch auxiliary contact signal port 1pc, 12Vdc external maintenance switch auxiliary contact signal port 1pc, 24Vdc switch driver signal output port 3pcs, 12Vdc switch auxiliary contact signal port 3pcs, 12Vdc external bypass switch auxiliary contact signal port 1pc, 12Vdc generator detection signal input port 1pc, 12Vdc input dry contacts 4pcs, Output dry contacts normally open 6pcs |
Electronic control unit | 2pcs |
Switches in the UPS housing | 4 pcs (Network Switch, Output Switch, Maintenance Switch, Bypass Switch) |
Touch color LCD display | UPS status, load level, battery level, input/output voltage, discharge timer and fault conditions |
Sound indication | Line failure, low battery, overload, system failure |
Sound and visual alarm | Line mode, Bypass mode, Low battery, Battery fault, Overload and UPS fault |
Dimensions, W×H×D (mm) | 2200×2000×850 |
Net weight (kg) | 2060 |
Operating temperature | 0-40°C |
Storage temperature | -25 - 40°C |
Working humidity | < 95% non-condensing |
Height* | <1500 m, power reduction at >1500 m |
Noise level | less than 72.9 dB |
* If the UPS is installed or used in a location where the altitude is higher than the maximum altitude, the output power will be derated by 1% for every 100m.
Products are constantly being improved. Specifications and appearance are subject to change without notice.

OOO "Ontek"
地点: Moscow region, Mytishchi, Kolpakova street, 42k3