VVG-P-HL
Cables comply with the requirements of GOST 31996-2012.
Fire hazard class according to GOST 31565-2012: O1.8.2.5.4.
Climatic version HL, placement categories 1-5 according to GOST 15150-69.
Operating temperature range from minus 60 °C to +50 °C;
Relative air humidity at a temperature of +35 °C up to 98%;
Laying and installation of cables without preliminary heating is carried out at a temperature not lower than minus 30 °C;
Permissible heating temperature of the cores during operation:
- long-term - no more than +70 °C;
- in overload mode – no more than +90 °C;
- maximum short circuit temperature +160 °C;
- under conditions of non-ignition during a short circuit no more than +350 °C (the duration of a short circuit should not exceed 5 sec.).
Test voltage at 50 Hz:
- for voltage 0.66 kV - 3 kV;
- for voltage of 1 kV - 3.5 kV;
The electrical resistance of current-carrying cores, recalculated for 1 km of cable length and a temperature of +20 °C, complies with GOST 22483-2012.
Minimum bending radius for gasket and installation:
- single-core cables - 10 cable diameters;
- multi-core cables - 7.5 cable diameters;
Construction length of cables with core cross-section:
- up to 16 mm2 - 450 m;
- from 25 to 70 mm 2 - 300 m;
- 95 mm2 - 200 m;
The warranty period is 5 years from the date of commissioning of the cable, but not later than 6 months from the date of manufacture;
Service life of at least 30 years.